SPZ11

SEPARATOR (STEAM AND GAS DRYER)
TYPE: SPZ-11
optional PN25 and DN25-150

Download product chart:



spz_11_en.jpg

CLICK ON IMAGE TO ZOOM

1. Application range
Maximum operating pressure:

  • Po max: 1,6 MPa

Test pressure:

  • PT: 3,6MPa

Maximum operating temperature:

  • To max: 300°C

Corrosion allowance:

  • c2=1,0 mm


2. Basic materials
Casing/ bottom:

  • boiler steel

Sockets/ flanges:

  • carbon steel

Baffle plates:

  • carbon steel

Optional anticorrosion coating:

  • zinc plated

3. Design
Connections:

  • flanged DN25 - DN150, face type B1 acc. to PN-EN 1092-1
    screwed Rp 1" - Rp 6" at the client's request
    butt weld ends S 1" - S 6"at the client's request
    flanges acc. to ANSI or DIN at the client's request
    K3 socket can be made in three options (see fig. page 24)

4. Characteristics
The steam separator is a pressure vessel where condensate is separated from the flowing steam (air).  Wet steam (air) together with impurities arrive to the separator  via socket "K1" and then the direction of the steam flow changes thanks to the specially shaped baffle plates installed there. Centrifugal force causes the separation of bigger density particles, condensate and solid impurities, which then drift onto the separator's walls  and then sink to its lowest part. Steam (air) exits via socket "K2". Separated condensate and impurities sink into the lower part of the separator and are carried away via:
  • Socket "K3" on which the most dirt resistant steam trap should be installed. It can be pointed sidewards or downwards depending on the type of  inverted bucket steam trap being used.
  • Socket "K4" (design - option 3) which is used to carry away impurities. It is bottomed with a blind flange but it can be modified in different ways. It can for example have some additional room for impurities to be collected or a valve to empty accumulating sediment. As a matter of servicing personnel safety the outlet flange should be turned on after the pressure in the separator has been reduced to atmospheric pressure.
Steam separators are used at the entrance of the heat receivers which have to be supplied with good quality steam: dry and without impurities. To trap temporary water swings they can also be installed at the boiler exit just behind its main valve. Air (gas) separators are used at the entrance of the air receivers (vertical apparatus, pneumatic drives, etc.) which also have to be supplied with good quality air. Because of high operating temperatures, the separator should be isolated. It should be installed on the pipeline only in the horizontal position (as per the drawing, according to the indicated medium flow direction).

5. Requirements and testing

Flanges connecting sizes acc. to PN-EN 1092-1; (DIN; ANSI/ASTM).
Face to face acc. to the table.
Pressure testing acc. to WUDT-UC-WO-B.
Certificate of conformity in acc. with PN-EN 10204.
Design acc. to WUDT-UC-WO-D.
Manufacturing acc. to WUDT-UC-WO-W.
Separators have been submitted for appraisal of conformity according to the Pressure Equipment Directive 97/23/EC.

6. Directions for ordering
When giving your order you should supply the following information:
  • medium,
  • the maximum operating pressure,
  • the maximum operating temperature,
  • type and size of the connections.

7. Additional information
  • 24 months warranty compulsory acc. to the conditions which are in the manufacturer's warranty card.
  • The manufacturer is able to undertake inspections and  repairs of the fittings as well as replacement of the internal elements if required.
  • All the requirements concerning the quality and technical specifications of the fittings should be taken into consideration in your order. With the fittings we provide  specification sheets (technical and quality) as follows: standard - conformity declaration, Installation, Operation and Maintenance Manual, at the client's request - certificate 2.2 or 3.1.

We reserve  the right to introduce some technical changes without notice.
 

 


 

150x70.png

Steam tracers
The Central European climate imposes special requirements concerning the protection of industrial transferring appliances In chemical plants, refineries, petrochemical and other plants in order to protect them from low temperatures. This kind of protection is guaranteed by steam tracing system, which is based on the trace lines.

przepustnice

Read more...
 

Inverted bucket steam traps
The WZ steam traps are inverted bucket steam traps. They operate thanks to difference in displacement of the float which is filled with condensate or a mixture of steam and water.

odwadniacze

Read more...
 

Wedge gate valves
Wedge gate valves Gate valves are designed for general use pipelines in industrial systems. They can be installed on pipelines In a vertical or horizontal position and operate only when fully open or closed. Medium can flow in both directions. Typically we produce gate valves with hand drive.

zasuwy

Read more...
 

Copyright (c) 2009. Zamkon
All rights reserved.
Created by JKEY ® Web Studio