Steam losses in drainage systems mean real financial losses

A leaking steam trap can waste steam over many operating hours. The assessment starts with checking equipment condition and then relating identified faults to the plant’s operating conditions.

Diagnostic measurement on installed equipment.
Diagnostic measurement on installed equipment.

What measurement contributes

Photographs show equipment diagnostics and a measurement set with a probe and headphones. Diagnostics include ultrasound testing and temperature assessment. These provide information about trap operation for further investigation or servicing. The condition of the particular device is the starting point for assessing the loss.

Assumptions change the financial result

The calculation tables assume 8,000 operating hours per year, 10% steam loss and pressure cases of 1.2 and 2.5 MPa. They illustrate how flow and operating time affect an annual result. A plant-specific calculation requires actual operating conditions and energy cost; transferring a single amount from an example calculation is insufficient.

Figures that need clarification

The tables label the price unit as “zł/GJ/h”. In the second table, 0.9 GJ/h at 0.5 Mg/h needs checking against the neighbouring entries. The price unit and the inconsistent entry must be clarified before a new calculation. Historical figures remain unchanged and are not used here for new calculations.